VLF Cable Test Sets

Filter

HVA28 & HVA28TD

Output voltage 29 kVpeak, 21 kVrms
Load 0.5 μF @ 0.1 Hz @ 20 kVrms
Weight 14 kg / 31 lbs

HVA34-1 & HVA34TD-1

Output voltage 34 kVpeak, 24 kVrms
Load 1.5 μF @ 0.1 Hz @ 24 kVrms
Weight 39 kg / 86 lbs

HVA45 & HVA45TD

Output voltage 45 kVpeak, 32.3 kVrms
Load 0.9 μF @ 0.1 Hz @ 32 kVrms
Weight 39 kg / 86 lbs

HVA45 & HVA45TD +4 kV

Output voltage 49 kVpeak, 34.6 kVrms
Load 0.9 μF @ 0.1 Hz @ 32 kVrms
Weight 39 kg / 86 lbs

HVA68TD

Output voltage 68 kVpeak, 48 kVrms
Load 2.1 μF @ 0.1 Hz @ 43 kVrms
Weight 63 kg / 139 lbs

HVA30-7

Output voltage 34 kVpeak, 24 kVrms
Load 6.0 μF @ 0.1 Hz @ 24 kVrms
Weight 57 kg / 125.6 lbs

HVA34

Output voltage 34 kVpeak, 24 kVrms
Load 0.9 μF @ 0.1 Hz @ 24 kVrms
Weight 20 kg / 44 lbs

HVA40-5

Output voltage 45 kVpeak, 32 kVrms
Load 5.0 μF @ 0.1 Hz @ 27 kVrms
Weight 57 kg / 125.6 lbs

HVA54-3

Output voltage 54 kVpeak, 38 kVrms
Load 3.0 μF @ 0.1 Hz @ 36 kVrms
Weight 57 kg / 125.6 lbs

HVA60

Output voltage 62 kVpeak, 44 kVrms
Load 1.0 μF @ 0.1 Hz @ 44 kVrms
Weight 57 kg / 125.6 lbs

HVA68-2

Output voltage 68 kVpeak, 48 kVrms
Load 2.0 μF @ 0.1 Hz @ 44 kVrms
Weight 57 kg / 125.6 lbs

HVA90

Output voltage 90 kVpeak, 64 kVrms
Load 1.0 µF @ 0.1 Hz @ 64 kVrms
Weight 127 kg / 280 lbs

HVA94

Output voltage 94 kVpeak, 66 kVrms
Load 0.9 µF @ 0.1 Hz @ 66 kVrms
Weight 128 kg / 282.2 lbs

HVA120

Output voltage 120 kVpeak, 85 kVrms
Load 0.5 µF @ 0.1 Hz @ 85 kVrms
Weight 198 kg / 436.5 lbs

VLF high voltage test sets of the HVA series from b2 electronics are the most advanced VLF AC/DC hipot test equipment of its kind available. They perform voltage withstand tests on MV and HV cables at frequencies from 0.01 Hz to 0.1 Hz and incorporate the lightest and the most compact VLF test sets of their kind.

b2 electronics offers the widest range of VLF test sets on the market, starting with the compact devices weighing only 14 kg / 31 lbs and a maximum output voltage of 21 kVrms / 29 kVpeak (HVA28) up to a van or trailer mounted device with 85 kVrms / 120 kVpeak (HVA120).

Characteristics

Unlimited operating time

HVA test sets are designed for continuous operation without any thermal limitations.

Dry system (up to 120 kV)

HVA test sets are constructed with non- arcing contacts and no need to change oil. This eliminates routine servicing and makes the test sets almost maintenance-free.

Compact & portable

Our HVA test sets are designed for maximum portability, resulting in widely applicable devices for any type of on-site use.

True modularity

All our HVA test sets can be easily extended to a complete diagnostics system by adding our PD, TD or PDTD series products at a later point of time. This keeps the initial investment low.

Your Benefits

  • Automatic load calculation and frequency selection (0.01 Hz - 0.1 Hz)
  • Pure sinusoidal output voltage (load-independent) over the entire power range
  • Easily exchangeable HV test lead
  • Breakdown voltage and load detection
  • Suitable for MV & HV cables with different insulations (XLPE, PILC, PE, EPR, etc.)
  • Safety: Dual Discharge Device (DDD) & integrated 12 kV backfeed protection
    (at 50 / 60 Hz)
  • Real time oscilloscope view of the output voltage on the HVA display
  • Programmable test sequences with a tailor-made software tool

We use cookies on our website. Some of them are technically necessary, while others help us to improve this website or provide additional functionality. By using it, you agree to our cookie policy.